Victron 12-165 GEL (24V Bank)
- Type: 12V 165Ah GEL (VRLA), configured as 24V bank
- Use: Legacy/aux battery bank for 24V systems
Installed
- Quantity: 4 units installed
- Bank arrangement: 2S2P (two series pairs in parallel, 24V nominal)
Configuration Notes
- Two 12V 165Ah GEL batteries in series for 24V nominal, with two such series strings in parallel (2S2P).
- Observe Victron recommended charge voltages for GEL chemistry.
- Ensure temperature-compensated charging if available.
Capacity
- Per battery:
12V × 165Ah = 1,980Wh
(1.98kWh)
- Bank topology:
2S2P
→ 24V nominal, Ah
sums in parallel: 165Ah × 2 = 330Ah
- Total energy (theoretical):
24V × 330Ah = 7,920Wh
(7.92kWh)
- Usable energy (typical guidance for GEL):
- 50% DoD (long life): ≈ 3.96kWh
- 80% DoD (shorter life): ≈ 6.34kWh
Datasheet
- External link: https://www.victronenergy.com/upload/documents/Datasheet-GEL-and-AGM-Batteries-EN.pdf
- Local copy: Datasheet (PDF)