Scotty V3 24/48V DC-DC Converter¶
- Type: Bidirectional or unidirectional DC-DC converter (Scotty V3)
- Use: Step-up/step-down between 24V and 48V systems
Installed¶
- Quantity: 2 units installed
- Role: Bridge between 24V GEL bank and 48V Meteor bank
Configuration Notes¶
- Document input/output voltage configuration and current limits.
- Note enable/ignition wiring, protections, and thermal derating.
- Record any CAN/serial settings and firmware versions.
Recommended Configuration¶
Context: Bridge a 48V LiFePO4 bank (Safiery Meteor, 1S16P) to a 24V GEL bank (Victron 12-165, 2S2P).
- Mode
- Direction: 48V → 24V (buck) enabled
- Reverse (24V → 48V): disabled (avoid charging LFP from GEL)
-
Parallel units: 2 identical units sharing load (set same targets)
-
24V Output (GEL charging targets at 25°C)
- Absorption voltage: 28.2–28.8 V
- 28.2 V for long life (≈14.1 V × 2)
- 28.8 V for cyclic use (≈14.4 V × 2)
- Float voltage: 27.6 V (≈13.8 V × 2)
- Absorption end: tail current ≈ 4% of C or time cap 2 h
- Tail current basis: 330 Ah bank → 0.04 × 330 ≈ 13 A
- If tail-current not supported, use time cap only
-
Temperature compensation (if supported): −48 mV/°C from 25°C
- (−24 mV/°C per 12 V block × 2 in series)
-
Current Limits
- 24V charge current (total for both Scottys): ≤ 66 A (≈0.2 C of 330 Ah GEL bank)
- Per-unit limit: ≤ 33 A each (or below unit’s continuous rating and wiring/fuse limits)
-
Suggested initial setting: 25–30 A per unit for cooler operation
-
48V Input (LFP source safeguards)
- Start charge threshold: ≥ 52.5 V
- Stop/hysteresis: ≤ 51.5 V (resume when above start threshold)
- Low-voltage hard stop: 50.0 V
- High-voltage limit: 58.4 V max (16S LiFePO4 full)
-
Note: With 2 units @ 30 A each on 24V side, input current ≈ 30 A × 24 V × 2 / (48 V × η) ≈ 30 A at 48 V (η≈0.95)
-
Protections & Control
- Enable/Ignition: wire to enable only when system is on and cooling available
- Thermal: ensure airflow; derate current above 40°C as per manual
- Fault actions: latch-off on OVP/UVP/OTP; require manual reset
Rationale: Voltages reflect Victron GEL datasheet targets and common LFP limits; current limited to ≈0.2 C for GEL longevity. Adjust per temperature and duty cycle.
Manuals¶
- Local manual: Scotty V3 24/48 Manual (PDF)
- If you prefer external hosting, add the URL here.
Wiring¶
- Standard wiring diagram (PDF): Scotty Wiring Diagram
Maintenance¶
- Inspect connectors, fusing, and ventilation path.
- Verify mounting hardware torque and check for thermal events.